The Minifluor product range consists of several indoor modular prefabricated units, air insulated up to 24 KV, which can be equipped with cutting and disconnecting devices such as:
- Three-position SF6 switch-disconnectors, FLUORSWITCH series.
- Three-position SF6 isolators, FLUORSWITCH series.
- Additional air-insulated earthing switches
- Vacuum or SF6 circuit breakers.
Electrical characteristics
Rated voltage | Ur [kV] | 12 | 17,5 | 24 |
Value of nominal isolation at operating frequency | ||||
between the phases and to ground | Ud [kV] | 28 | 38 | 50 |
between open contacts | Ud [kV] | 32 | 45 | 60 |
Rated lightning impulse withstand voltage | ||||
between the phases and to ground | Up [kV] | 75 | 95 | 125 |
between open contacts | Up [kV] | 85 | 110 | 145 |
Rated frequency | Hz | 50/60 | ||
Nominal thermal current of main busbars | Ir [A] | 400 – 630 – 800 – 1250 | ||
Rated short-time current allowed | ||||
for 1 s | Ik [A] | fino a 20 KA | ||
for 3 s | Ik [kA] | 12,5 – 16 | ||
Rated peak current | Ip [kA] | 31,5 – 40 – 50 | ||
Internal arc withstand current 1 s | [kA] | 16 | ||
Gas pressure (at 20°) of the switch disconnector/line-side isolator | psw [MPA] | 0,13 |
MINIFLUOR MAIN CHARACTERISTICS
- Wide range of functional units
- Modularity
- Versions with internal arc protection (upon request)
- Mechanical and electrical interlocks available for maximum safety
- Compact design and optimum space utilisation
- Possibility to be pushed against the wall
- Easy installation and simple maintenance
- Product certifications, Acceptance and Type Tests
FIELDS OF APPLICATION
MINIFLUOR switchboards are used for medium voltage secondary power distribution: transforming substations controlling and protecting lines/transformers.
Considering their compact design, they are specially recommended for indoor installation, even in small rooms and prefabricated substations / CONTAINERS.
EXAMPLES OF APPLICATIONS
- Power supply systems
- Wind power plants
- Photovoltaic systems
- Underground and railway plants
- Electric power station
- Industry
- Ports, airports, hospitals, etc
STANDARDS
The equipment complies with the following standards:
- CEI EN 62271-200
- IEC 62271-200
More specifically, Minifluor switchboards are classified as follows:
- Service continuity: LSC2A
- Classification of partitions: PM
Internal arc: IAC AFLR (upon request only)